Features
Available analogue inputs: RTD, TC, Voltage, Resistance and Current
Two independent threshold programmable as both high alarm or one high and one low alarm
Galvanic isolated among the three ways
Trip level and hysteresis adjustable by potentiometer
Delay time adjustable by potentiometer up to 25 sec.
Two relays SPDT 250Vac, 2A
High accuracy
EMC compliant – CE mark
Suitable for DIN rail mounting in compliance with EN-50022 and EN50035
General Description
The converter DAT 5024 is able to accept on its input a wide range of normalised voltage signals, normalised current signals coming from both active and
passive current loop, signals coming from RTDs, Thermocouples and resistance sensors.
The input type and the input range are fixed: refer to the section “Technical Specifications”, table “ Input type ” to order the device.
The Threshold 1 is programmed as high alarm, while, by dip-switches, it is possible to set the Threshold 2 either as high or low alarm.
The trip level of each threshold can be adjusted by the potentiometers and checked by the test-points located on the front of the device.
It is possible to adjust by potentiometers also the values of the hysteresis level and delay time.
The isolations eliminate the effects of all ground loops eventually existing and allows the use of the converter in heavy environmental conditions found in
industrial applications.
It is housed in a plastic enclosure of 20.5 mm thickness suitable for DIN rail mounting in compliance with EN-50022 and EN-50035 standards.